Before you change Global Scan thresholds, refer to the table below for a description of each field that you can control and the associated setting name that is used later in this article.

Performance FieldDescriptionDataStore Setting Nameuptime.conf Setting Name
TOTThe overall CPU % busy.

gs_cpu_warn

gs_cpu_crit

globalscan.cpu.warn

globalscan.cpu.crit

% UsedThe capacity of the file system that is most full on the element.

gs_diskfull_warn

gs_diskfull_crit

globalscan.diskfull.warn

globalscan.diskfull.crit

% BusyThe work time of the busiest spindle on the element.

gs_diskbusy_warn

gs_diskbusy_crit

globalscan.diskbusy.warn

globalscan.diskbusy.crit

Swap UsedTotal swap space used.

gs_swap_warn

gs_swap_crit

globalscan.swap.warn

globalscan.swap.crit

Each field has two setting names: one to control the warning (yellow) threshold and another to set the critical (red) threshold. You can modify one or both settings. The setting to update for warning thresholds includes the word "warn" in the setting and the critical threshold setting includes the word "crit" in the setting name.

Changing thresholds for all elements

To change the current thresholds for all elements within your UIM installation, complete the following steps:

  1. Connect to your up.time DataStore using an ODBC or database tool. Assuming that you have installed Uptime Infrastructure Monitor in the default location, you can access the DataStore at the command line using the following commands:
    Code Block
    languagesql
    «change to the Uptime installation directory» 
    cd mysql
    cd bin
    ./mysql -u uptime --password=uptime -P 3308 --protocol=TCP uptime
  2. After you login to the UIM DataStore, run a command to update the threshold that you want to use with all elements. The command format and an example are detailed below. Replace the «field» text in the example below with a value from the DataStore setting name column in the table above. Replace the «new value» text in the example below with your new threshold setting (decimal values are not permitted for thresholds).
    Info

    All mysql commands assume that you are using a MySQL DataStore. The format of the commands may differ slightly for Oracle or SQL Server databases.

    Code Block
    languagesql
    mysql» update entity set «field»=«new value»;
    
    Example
    mysql» update entity set gs_swap_warn=50 
    mysql» update entity set gs_swap_crit=75
  3. Run the command above for each threshold value that you want to change. When you are finished, use the exit; command to return to the command line.
  4. Refresh your Global Scan view to see the new settings.

Changing thresholds for a single element

To change the current thresholds for a single element within your UIM installation

...

Changing the default values for new elements

Configure To configure different default GlobalScan Global Scan threshold settings for all new elements that you add to Uptime Infrastructure Monitor by completing the following stepsUIM

  1. On your monitoring station system, open the uptime.conf file in a text editor.

...

  1. The uptime.conf file is located in the base

...

  1. UIM installation folder.
  2. Locate the following lines in the file:
    Code Block
    languagesql
    globalscan.cpu.warn=70 
    globalscan.cpu.crit=90 
    globalscan.diskbusy.warn=70 
    globalscan.diskbusy.crit=90 
    globalscan.diskfull.warn=70 
    globalscan.diskfull.crit=90 
    globalscan.swap.warn=70 
    globalscan.swap.crit=90
  3. Edit the values after the = character to reflect the default

...

  1. Global Scan thresholds that you want to use for new elements added to

...

  1. UIM.
  2. Save the file, and then exit the text editor.
  3. Restart the

...

  1. UIM core service.
    On Solaris and Linux monitoring stations, restart the uptime_core service. On Windows monitoring stations, restart the up.time Data Collector service.
    All elements that you add to

...

  1. UIM use the

...

  1. Global Scan thresholds specified in the uptime.conf file.